Wall Type Indicator Post
Wall Type Indicator Post Definition and Components
Wall Type Indicator Post Model 9101 is a wall-mounted pressure indicating device used in fire protection and industrial systems to visually display the status (open/closed) of buried or concealed underground valves. Wall Post Indicator Valve provides clear visual indication of valve position without excavation.
Main Components:
Indicator Head Assembly
- Target Plate: Red/white or yellow/black rotating disc
- Indicator Glass: Clear protective lens
- Position Markings: "OPEN" and "SHUT" labels
- Lighting Kit (Optional): Internal illumination for low-light areas
Drive Mechanism
- Drive Shaft: Stainless steel rod connecting to underground valve stem
- Gear Box: Converts rotary motion (if needed)
- Adjustable Coupling: For precise alignment
Housing & Mounting
- Weatherproof Housing: Aluminum or stainless steel enclosure
- Wall Bracket: Adjustable mounting plate
- Conduit Entry: For optional electrical connections
- Drain Holes: Prevents moisture accumulation
Connection System
- Extension Rod: Connects to buried valve stem
- Universal Joints: For angular misalignment
- Rod Guides: Support and alignment
- Rodding Access Cover: For maintenance access
Role, Characteristics, and Application Scenarios of Wall Type Indicator Post in Pipelines
Post Indicator Valve Primary Functions:
- Visual Indication: Clearly shows if underground valve is OPEN or SHUT
- Remote Monitoring: Allows valve status checking without excavation
- Position Confirmation: Verifies valve position for maintenance/testing
- Tamper Evidence: Shows if valve has been operated
Operational Features:
- Direct Mechanical Link: No electronics required for basic operation
- Weatherproof Design: Suitable for outdoor installation
- Easy Installation: Mounts on walls, columns, or posts
- Maintenance-Free: Sealed bearings, corrosion-resistant materials
- Optional Features: Lighting, switch contacts for remote signaling
Application Scenarios:
- Fire Protection Systems: Indicating post for buried fire main valves
- Water Utilities: Municipal water distribution control valves
- Industrial Plants: Process line isolation valves
- Irrigation Systems: Main control valves
- Marine Facilities: Dock hydrant control valves
Wall Type Indicator Post Standards: Materials, Design, and Connections
Material Standards:
- Housing: Aluminum alloy (EN AW-6060) or Stainless Steel 304/316
- Target Plate: Anodized aluminum or ABS plastic
- Drive Shaft: Stainless Steel 304 (ASTM A276)
- Bearings: Sealed stainless steel or bronze
- Fasteners: Stainless steel A2/A4 grade
Design Standards:
- UL/FM Approved: For fire protection applications
- AWWA C504: Standard for indicator posts
- BS 5163: British standard for indicator plates
- ISO 9001: Quality management system
- IP Rating: IP65 minimum for outdoor use
Fire Valve Connection Standards:
- Valve Connection: Typically 1" square or 1-1/4" square for valve stem
- Extension Rod: 3/4" or 1" diameter, threaded connections
- Mounting: Wall bracket with slotted holes for adjustment
- Electrical: 1/2" NPT conduit entry for optional switches
How to Select Wall Type Indicator Post
Purchasing Steps:
Technical Specification:
- Valve stem size and type (square, hex, spline)
- Required extension length (ground to mounting point)
- Environmental conditions (coastal, chemical, temperature)
- Optional features (lighting, limit switches)
- Color scheme (standard: red/white or yellow/black)
Supplier Selection:
- Choose manufacturers with UL/FM listings
- Verify experience with similar installations
- Check customization capabilities
- Review installation support services
Documentation Requirements:
- UL/FM certificates
- Material certifications
- Installation drawings
- Operation and maintenance manuals
- Testing certificates
Commercial Considerations:
- Lead Time: 2-4 weeks standard
- Payment: Typically net 30
- Warranty: 2-5 years
- Shipping: Usually small parcel
- MOQ: 1 unit typically
Pre-Shipment Inspection for Export Wall Type Indicator Post and Key Considerations
Inspection Checklist:
| Area | Procedure | Acceptance Criteria |
| Visual | Exterior inspection | No damage, clean finish |
| Mechanical | Rotate mechanism | Smooth operation, no binding |
| Target Plate | Check colors/legibility | Clear "OPEN/SHUT" markings |
| Materials | Verify certifications | Match specifications |
| Weatherproof | Check seals/gaskets | Complete, undamaged |
| Optional Features | Test lighting/switches | Function as specified |
| Packaging | Check protection | Adequate for transport |
Export Precautions:
- Corrosion Protection: VCI paper for internal components
- Shaft Protection: Plastic caps on connection ends
- Glass Protection: Bubble wrap or foam protection
- Documentation: Include multilingual installation guide
- Small Parts: Bag and label all fasteners separately
Wall Type Indicator Post Material List
| Name of parts | Material |
| Body | Cast iron/Ductile iron |
| Cover | Cast iron/Ductile iron |
| Operating Nut | Bronze C83600 |
| Target Carrier Nut | Bronze C83600 |
| OPEN Sign | Cast Aluminium |
| SHUT Sign | Cast Aluminium |
| Window Class | Plexiglas |
| Gasket | EPDM |
| Plug | Carbon Steel ASTM A105/A105M |
| Snap Ring | Carbon Steel AISI1066 |
| Eye Bolt | Carbon Steel ASTM A105/A105M |
| Hand wheel OD356 | Ductile iron |
| Extension Rod | Carbon Steel ASTM A1045 |
| Coupling | Ductile iron |
| Bolt | Carbon Steel ASTM A105/A105M |
| Nut | Carbon Steel ASTM A105/A105M |
| Plain | Carbon Steel ASTM A105/A105M |
| Lead Ring | |
| Pin | SS304 |